This tutorial will help with wiring checks

Step-by-step guide


  1. Have a power meter check the voltage after writing 50% on the damper cmd within ankalytik connector view.
  2. If the analog input is not changing check wiring
    1. Make sure wiring on the actuator is as follows red white blue yellow and on the other side where it connects to the EAC is red blue yellow-white.

T is common

~ 24VAC

Y is input

U is output 2-10V



Check 10V is being red between T and U when 100% is written from the back-end.